Motor Vibration and Noise: 8 Causes and How to Find Them

Motor vibration and noise: causes and how to find them

A vibrating or noisy motor is asking for attention. The cause may be mechanical, such as a worn bearing or misalignment, or electrical, such as an unbalanced supply. Left alone, vibration damages bearings, couplings and windings, and a small problem becomes a breakdown. This guide shows how to read the noise, two simple tests that split the problem in half, eight common causes, and a checklist.

Safety first: Lock out the power before you touch the motor, the coupling or the guards. Never run a motor with the guards removed. Voltage and current measurements on live equipment must only be done by a qualified person, following local rules.

What does the noise tell you?

Four motor noises, what they often mean and what to check

The sound gives you a first idea before you measure anything:

  • Squeal or whine: a dry or worn bearing, or the switching tone of a drive.
  • Rumble or grinding: a damaged bearing.
  • Low hum: often electrical, such as unbalanced voltage, a missing phase or a winding fault. A hum at twice the supply frequency (100 or 120 Hz) points to an electrical cause.
  • Knock or click: looseness, a worn coupling or a fan rubbing its cover.

Two simple tests

Two simple tests to tell electrical from mechanical vibration, and motor from machine

These two tests split the problem in half:

  1. Switch off while the motor runs. If the vibration stops at once, the cause is electrical (voltage, windings or rotor). If it fades slowly as the motor slows down, the cause is mechanical (balance, alignment, bearings or looseness).
  2. Run the motor uncoupled. With the load disconnected, the shaft key secured and your procedures followed, run the motor alone. If the vibration stays, the problem is in the motor. If it disappears, look at the driven machine, the coupling or the alignment.

8 common causes

1. Unbalance

A rotor, fan or coupling half that is out of balance, or one with dirt built up on one side, makes the motor vibrate at its running speed.
Fix: Clean the fan and the rotating parts. If the vibration remains, have the part balanced.

2. Misalignment

When the motor and the driven machine shafts are not in line, the coupling is forced to flex on every turn. It creates vibration, heat and bearing wear.
Fix: Re-align the shafts with a dial indicator or a laser tool, and check the coupling for wear.

3. Worn or damaged bearings

Worn bearings, poor lubrication, too much grease or contamination cause noise, heat and vibration.
Fix: Check the noise and temperature at each end bracket. Lubricate as the manufacturer says (never over-grease), and replace worn bearings.

4. Looseness and soft foot

Loose mounting bolts, a weak or cracked base, or a motor foot that doesn’t sit flat (“soft foot”) let the motor shake.
Fix: With the power locked out, check and tighten the bolts to the specified torque, and check that all feet sit flat on the base. Shim where needed.

5. A worn coupling or belt problems

A worn coupling element, a belt that is too loose or too tight, or a worn pulley adds noise and vibration.
Fix: Inspect and replace worn parts, and set the belt tension as specified.

6. Voltage imbalance or phase loss

An unbalanced or missing phase makes a motor hum and vibrate at twice the supply frequency (see our guides on voltage imbalance and on motors that won’t start).
Fix: A qualified person measures the voltage and current on all three phases.

7. Rotor or winding problems

Broken rotor bars or shorted winding turns can cause a pulsing noise, changes in speed and unequal currents.
Fix: These need specialist tests, such as current analysis and winding tests. Call a motor repair specialist.

8. Drive-related noise and resonance

A drive can add a high-pitched tone from its switching frequency, and some speeds can make the motor or the machine resonate.
Fix: Adjust the switching frequency within the manufacturer’s limits, or set a skip frequency to avoid the resonant speed (see our guide on VFD fault codes).

Step-by-step troubleshooting

Seven-step checklist for troubleshooting motor vibration and noise

  1. Describe the vibration and the noise: where, when, how loud, and what kind of sound.
  2. Do the power-off test.
  3. With the power locked out, check the mounting and look for looseness.
  4. Check the coupling and the alignment.
  5. Check the bearings: noise, heat, grease and shaft play.
  6. Check voltages and currents (qualified person).
  7. Measure the vibration with a vibration meter, and compare it with the manufacturer’s limits and with earlier readings.

Mistakes to avoid

  • Running a vibrating motor “until the shift ends”. Damage grows quickly.
  • Over-greasing the bearings. Too much grease causes heat and noise.
  • Ignoring a change in sound. A new noise is information.
  • Tightening belts too much. This overloads the bearings.
  • Not recording readings. A trend over time shows problems early.

Quick reference

What you notice Likely cause
Vibration at running speed Unbalance, resonance
Strong vibration along the shaft, hot coupling Misalignment
Rumble or grinding, hot end bracket Damaged bearing
Hum at 100 or 120 Hz Electrical: voltage imbalance, winding fault
Knock or click Looseness, worn coupling, rubbing fan

When to call a specialist?

If the vibration is strong, if you suspect rotor or winding problems, or if the noise returns after you fix the obvious causes, stop and call a motor specialist. A rebuild planned in advance costs far less than an unexpected failure.

What was the most surprising cause of vibration you have found? Share it in the comments below.


Print this checklist and keep it in your toolbox or your panel.

Download the free checklist (PDF)

Wednesday, October 21, 2026

Circuit Breaker Keeps Tripping: 8 Causes in an Industrial Panel

Circuit breaker keeps tripping: 8 causes in an industrial panel

A circuit breaker that keeps tripping is doing its job: it opens when something is wrong. Resetting it again and again, or fitting a bigger one, hides the problem and can lead to damaged equipment or a fire. This guide explains how to read the trip, the eight most common causes in an industrial panel, and a step-by-step way to find the real one.

Safety first: A short circuit can cause an arc flash when you re-energize, and a breaker that has cleared a large fault may be damaged. Lock out the power, verify it is dead, and follow your company’s procedures and protective equipment rules. Measurements and thermal checks on live panels must only be done by a qualified person.

Reading the breaker handle

Breaker handle in the ON, tripped and OFF positions
A breaker handle has three positions. ON means closed, OFF means open by hand, and a tripped breaker usually rests in a middle position between the two. To reset a tripped breaker, move the handle fully to OFF first, then to ON. Reset it once, and only after you have checked for an obvious cause. If it trips again immediately, leave it off and investigate.

Which kind of trip is it?

Thermal, magnetic and earth leakage trips compared: how they trip, what they mean and what to check


Most breakers combine different protections, and how the breaker tripped is your best clue:

  • Thermal (overload): it trips after some time, often minutes after a load starts, and the breaker may feel warm. The current was above the rating for too long.
  • Magnetic (short circuit): it trips instantly, often with a loud bang. There was a very high fault current between conductors.
  • Earth leakage (ground fault): it trips instantly or at random, often in damp conditions. Current is leaking to earth.

8 common causes

1. Overload

The circuit carries more current than the breaker rating for too long, for example a motor with a mechanical problem, or loads added to an existing circuit.
Fix: A qualified person measures the load current on each phase and compares it with the breaker rating. Find out why it is high (see our guide on motors running hot, and the one on voltage imbalance).

2. Short circuit

Damaged cable insulation, a failed component, metal debris or a loose strand of wire can create a direct short between conductors. The breaker trips instantly.
Fix: With the power locked out, inspect the circuit and test the insulation resistance between phases and to earth. Don’t reset until you find the cause, and check the breaker for damage afterward.

3. Ground fault or earth leakage

Moisture in a motor terminal box, damaged cable insulation or a failing winding lets current flow to earth. Drives and their filters also create small leakage currents, which can trip an earth leakage device that is not suited for them.
Fix: Test the insulation to earth with a megohmmeter. Check for water and damage. If a drive is involved, ask the manufacturer which type of earth leakage protection is suitable.

4. Starting current and the wrong trip curve

Motors and transformers draw a large inrush current at start. A breaker with a fast curve may trip each time, even if the circuit is healthy.
Fix: Check that the breaker type and curve suit the load. For motors, a motor protection breaker is often the right device. Follow the design or the manufacturer’s data.

5. Loose connections and overheating

A loose lug or busbar connection creates resistance and heat. The breaker heats up from the connection and trips at a lower current than its rating.
Fix: With the power locked out, retighten connections as specified and look for discoloration. A thermal camera, used by a qualified person on the live panel, helps to find hot spots.

6. High temperature or crowded breakers

Thermal breakers are sensitive to the temperature around them. In a hot, closed enclosure, or when many breakers are mounted side by side, they can trip below their rated current.
Fix: Check the enclosure temperature and ventilation. Check the manufacturer’s derating data for grouped breakers.

7. Wrong or changed settings

On breakers with adjustable trip units, someone may have changed the current or time settings, or the settings may not match the load after a change to the plant.
Fix: Compare the settings with the design values. Don’t raise them to stop the tripping without an engineering check.

8. A worn or damaged breaker

Breakers wear out. After a large fault, or after years of use, a breaker can trip below its rating or fail to hold.
Fix: If everything downstream checks out and the breaker still trips, test or replace it. Use a breaker of the same type and rating.

Step-by-step troubleshooting

Seven-step checklist for troubleshooting a circuit breaker that keeps tripping

  1. Note how the breaker tripped: handle position, trip flag and the time after starting.
  2. Lock out the power and look for heat marks, a burnt smell and damaged cables.
  3. Check the breaker rating, curve and settings against the load.
  4. Test the insulation downstream, phase to phase and phase to earth.
  5. Check terminals and temperature (qualified person).
  6. Measure the load current and compare it with the rating (qualified person).
  7. Reset once, then reconnect the loads one at a time and test.

Mistakes to avoid

  • Resetting again and again. Each reset onto a fault is a risk.
  • Fitting a bigger breaker. The cable and the equipment are then no longer protected.
  • Raising the trip settings without an engineering check.
  • Ignoring a warm breaker. Heat means a problem somewhere in the connection.
  • Bypassing the breaker in any way.

Quick reference

What you notice Likely cause
Trips after minutes under load, breaker warm Overload, heat, loose terminal
Trips instantly when closed Short circuit or ground fault
Trips when a motor starts Inrush current, wrong curve or setting
Trips at random, often in damp conditions Earth leakage, moisture, drive filters
Trips below its rating and runs hot Loose connection, high ambient, worn breaker

When to call a specialist?

If the breaker trips immediately after a reset, if you smell burning or see damage, or if you can’t find the cause, stop and call a qualified electrician. A fuse that keeps blowing follows similar logic, so see our guide on fuses that keep blowing.

Which kind of trip have you seen most often in your plant? Share it in the comments below.


Print this checklist and keep it in your toolbox or your panel.

Download the free checklist (PDF)

Fuse Keeps Blowing: 8 Causes and How to Find the Real Problem

Fuse keeps blowing: find the real cause safely

A fuse that keeps blowing is frustrating, and the temptation is to fit a bigger one. Don’t. A fuse is the deliberate weak point of a circuit: it blows to protect cables, equipment and people. If it blows again and again, something is wrong downstream. This guide shows you how to read a blown fuse, the eight most common causes, and a safe way to find the real problem.

Safety first: Lock out the power before you remove or replace any fuse, and verify that the circuit is dead. A short circuit can cause an arc flash when you re-energize, so follow your company’s procedures and wear the required protective equipment. Measurements on live equipment must only be done by a qualified person. Never fit a larger fuse, a wire or a bypass.

A blown fuse is a symptom

The fuse did its job. Your task is to find out what pushed the current above its limit: an overload, a short circuit, a ground fault, or a problem with the fuse or its holder.

Read the blown fuse

Three signs on a blown fuse and what each one usually means

How the fuse failed gives you a first clue. These are typical signs, and you should always confirm with measurements:

  • Blackened or burst body: usually a large short circuit or ground fault.
  • Element melted in the middle: usually an overload that lasted for some time.
  • Heat marks on the end caps or the fuse holder: usually poor contact or a loose connection.

8 common causes

1. A sustained overload

The circuit carries more current than the fuse is rated for, for long enough to melt the element. A motor with a mechanical problem, or too many loads on one circuit, are typical causes.
Fix: A qualified person measures the load current and compares it with the fuse rating. Find out why the load is high (see our guide on motors running hot).

2. A short circuit between phases or to neutral

Damaged cable insulation, a failed component, metal debris or a tool left in a panel can create a direct short. The fuse blows immediately and violently.
Fix: With the power locked out, inspect the cables, terminals and components downstream, and test the insulation. Don’t re-energize until the short is found.

3. A ground fault

Moisture in a motor terminal box, a damaged cable or failed winding insulation lets current flow to earth.
Fix: With the circuit disconnected, test the insulation resistance of each cable and motor phase-to-earth with a megohmmeter. Look for water and damage.

4. Starting current and the wrong fuse type

Motors and transformers draw a large inrush current when they start. A fast-acting fuse on such a circuit may blow every time.
Fix: Use the type the manufacturer or the design specifies, such as a time-delay or motor-rated fuse. Never use a larger rating just to avoid blowing.

5. Loose connections or a poor fuse holder

A loose terminal or a worn fuse holder creates resistance and heat. The fuse is heated from outside, so it ages and blows earlier than it should.
Fix: Retighten the connections as specified, and replace the fuse holder if it shows discoloration or lost spring tension.

6. A fuse that is too small or the wrong type

Sometimes the fuse was never right for the circuit: an undersized rating, a wrong voltage rating, or a type that doesn’t suit the load.
Fix: Compare the fuse with the equipment data and the circuit design. The rating must suit the load and never exceed what the cable can carry.

7. Phase loss or voltage imbalance

In a three-phase circuit, a missing or weak phase pushes extra current through the others (see our guide on voltage imbalance).
Fix: Measure the voltage on all three phases and check the other fuses, contactors and connections.

8. Heat, vibration and ageing

Fuses carry less current in a hot enclosure. Repeated surges and vibration can also fatigue the element over time. Inside drives and power supplies, a failing component can draw excess current.
Fix: Check the enclosure temperature, ventilation and mounting. If a fuse inside a drive or a power supply blows, look at the equipment manual and call a specialist.

Choose the right fuse

Four things to check before replacing a fuse: current, type, voltage and what never to do
Before you replace a fuse, check four things. The current rating must be above the normal load current, and never above what the cable can carry. The type must suit the load, for example fast-acting for electronics, and time-delay or motor-rated for motors and transformers. The voltage rating must be at least the circuit voltage, with enough breaking capacity for the maximum fault current. And never fit a bigger fuse, a wire or a bypass to stop it from blowing.

Step-by-step troubleshooting



Seven-step checklist for troubleshooting a fuse that keeps blowing
  1. Lock out the power and note the fuse rating, voltage, type and the circuit it protects.
  2. Examine the blown fuse and its holder.
  3. Look for visible damage downstream: cables, terminals, debris and moisture.
  4. Test the insulation of the circuit, phase to phase and phase to earth.
  5. Measure the load current and compare it with the fuse rating (qualified person).
  6. Reconnect one section at a time, with a new fuse of the correct type and rating.
  7. Review the fuse rating and type against the load, the cable and the manufacturer’s data.

Mistakes to avoid

  • Fitting a larger fuse. This leaves the cable and equipment unprotected, and can lead to fire.
  • Using a wire or a bypass instead of a fuse. Never do this.
  • Replacing the fuse again and again. Each re-energizing on a fault is a risk.
  • Mixing fuse types in the same circuit, or using a different rating “because it fits”.

Quick reference

What you notice Likely cause
Blows immediately when energized Short circuit or ground fault
Blows when a motor starts Inrush current, wrong fuse type, mechanical problem
Blows after running for a while Overload or high temperature
Blows at random Loose connection, vibration, poor fuse holder
One fuse in a three-phase circuit keeps blowing Phase problem or voltage imbalance

When to call a specialist?

If the fuse blows immediately after you replace it, if you can’t find the cause, or if the fuse is inside a drive or a power supply, stop and call a qualified electrician or the manufacturer. Don’t keep trying.

Have you tracked down a fuse problem with an unusual cause? Share it in the comments below.


Print this checklist and keep it in your toolbox or your panel.

Download the free checklist (PDF)

Three-Phase Voltage Imbalance: Causes, Effects and How to Check It

Three-phase voltage imbalance: causes and effects on motors

On a three-phase supply, the three line voltages should be nearly equal. When they are not, the supply is “unbalanced”. It is easy to miss, because the motor still runs. But it runs hotter, wastes energy and wears out sooner. This guide explains how to calculate the imbalance, why even a small percentage matters, what causes it, and how to find the source.

Safety first: Measurements on live equipment must only be done by a qualified person, with suitable instruments, following local rules and your plant’s procedures. Lock out the power before you touch connections, fuses or terminals.

What is voltage imbalance?

Voltage imbalance (or unbalance) means the three phase-to-phase voltages are not equal. For example, a nominal 400 V supply might read 400 V, 408 V and 392 V. It is expressed as a percentage.

How to calculate voltage unbalance

Worked example of calculating voltage unbalance with three line-to-line readings

Use this method:

  1. Measure the three line-to-line voltages at the motor terminals, with the motor running under load.
  2. Calculate their average.
  3. Find the largest difference between any one reading and the average.
  4. Divide that difference by the average and multiply by 100.

Example: 400 V, 408 V and 392 V give an average of 400 V. The largest deviation is 8 V, so the unbalance is 8 ÷ 400 × 100 = 2 %.

As a guide, aim for less than 1 %. Many motor standards require the motor load to be reduced above 1 % and advise against running above 5 %. Check your motor manufacturer’s documentation for its own limits.

Why a small imbalance matters?

How a small voltage imbalance leads to current imbalance, overheating and early motor failure

The key problem is that current is much more sensitive than voltage. As a rule of thumb, the current imbalance can be about 6 to 10 times the voltage imbalance. A 2 % voltage unbalance can therefore mean a current unbalance of 12 % to 20 %. The most heavily loaded winding gets hot, and as a rule of thumb, a 3.5 % voltage unbalance can raise the temperature of the hottest winding by roughly 25 %.

The effects are:

  • Higher winding temperature and faster ageing of the insulation
  • Lower efficiency and higher energy cost
  • Vibration and extra noise
  • Nuisance tripping of overload relays, and early motor failure

If you have a motor that runs hot with no obvious reason, see our guide on motors running hot.

Common causes

1. Unequal single-phase loads

Lighting, heaters and small machines connected to only one or two phases pull those phases down.
Fix: Redistribute the single-phase loads so each phase carries about the same.

2. Loose or corroded connections

A poor connection adds resistance on one phase, which creates a voltage drop and heat.
Fix: With the power locked out, check and retighten terminals, lugs and busbar connections. Look for discoloration from heat.

3. A blown fuse or a worn contact

A blown fuse, a worn contactor contact or a damaged breaker pole on one phase unbalances the supply to the motor, and in the worst case causes a missing phase (see our guide on motors that won’t start).
Fix: Check fuses, contactors and breakers on all three phases and replace damaged parts.

4. Faulty power factor correction capacitors

A blown fuse in a capacitor bank, or a failed capacitor, can unbalance the supply.
Fix: Check the capacitor bank, its fuses and its controller.

5. Supply or transformer problems

Unequal transformer taps, an open-delta connection or an imbalanced utility supply can produce unbalance before it reaches your equipment.
Fix: Measure at the source. If the imbalance is already present there, involve the electrical supplier or the transformer maintenance team.

6. Unequal cables

Long runs, unequal lengths or different cable sizes on the three phases cause unequal voltage drops.
Fix: Check the cable sizes and lengths against the design, and replace damaged cables.

Step-by-step troubleshooting

Seven-step checklist for finding the cause of voltage imbalance

  1. Measure the three line voltages at the motor, with the motor running (qualified person).
  2. Calculate the unbalance percentage.
  3. Measure the current on each phase and compare it with the average and the nameplate (qualified person).
  4. Compare the voltage at the source with the voltage at the motor, to see where the imbalance appears.
  5. With the power locked out, check connections, fuses and contacts.
  6. Check the loads on the supply, including single-phase loads and capacitor banks.
  7. Use the lead rotation test, described below, to separate a supply problem from a motor problem.

The lead rotation test

This test tells you whether the imbalance comes from the supply or from the motor.

  1. Measure and note the current on each of the three leads, with the motor running (qualified person).
  2. Lock out the power. Move each supply lead one terminal over, in the same direction, for example L1 to T2, L2 to T3 and L3 to T1. This keeps the direction of rotation unchanged. Never swap just two leads, because this reverses the motor.
  3. Restart and measure the current on each lead again.
  4. If the highest current follows the supply lead (it moved to a different motor terminal), the cause is in the supply. If it stays on the same motor terminal, the cause is in the motor.
  5. Restore the original connections afterward.

Mistakes to avoid

  • Measuring only at the panel. The imbalance may appear only at the motor, after a bad connection or a long cable.
  • Measuring with no load. Many problems show only under load.
  • Relying only on the overload relay. It may not trip until the damage is done. Consider a phase failure and unbalance monitoring relay.
  • Ignoring “small” numbers. Even a 2 % to 3 % voltage unbalance matters in the long term.

Quick reference

Voltage unbalance What to do
Below 1 % Good. Keep monitoring.
1 % to 2 % Find the cause and fix it at the next opportunity.
2 % to 5 % Reduce the motor load as the manufacturer advises, and fix the cause soon.
Above 5 % Do not run the motor until the cause is found.

When to call a specialist?

If the imbalance is present at the source, if you can’t find the cause, or if you are not sure how to work safely, stop and call a qualified electrician or your supplier. The cost of a visit is far lower than a failed motor.

Have you found a surprising cause of voltage imbalance? Share it in the comments below.


Print this checklist and keep it in your toolbox or your panel.

Download the free checklist (PDF)

VFD Fault Codes Explained: Overcurrent, Overvoltage and Undervoltage

VFD fault codes explained: OC, OV and UV in plain English

A variable frequency drive (VFD) that trips on overcurrent, overvoltage or undervoltage can stop a whole line. The display shows a short code, but the code only tells you what the drive measured, not why. This guide explains the three most common faults in plain English, when each one usually appears, and how to find the cause step by step.

Important: Names and codes differ between brands. You may see “OC”, “OV”, “UV”, or numbers such as “F001”, depending on the manufacturer. Always look up the exact code in your drive’s manual. The causes in this guide apply to all brands.

Safety first: A drive’s DC bus capacitors can hold a dangerous voltage after the power is switched off. Lock out the power, then wait for the time given in the drive’s manual (often several minutes) and check that the DC bus is discharged before you open the drive or touch its terminals. Measurements on live equipment must only be done by a qualified person, following local rules.

How a drive works in 30 seconds

Inside a VFD: rectifier, DC bus, inverter and motor, with where UV, OV and OC faults appear

A drive first turns the AC supply into DC (the rectifier). It stores that DC in capacitors (the DC bus). Then it builds a new AC output for the motor at the speed you want (the inverter). Each of the three faults points to a different part:

  • Undervoltage: the DC bus is too low, usually because of a supply problem.
  • Overvoltage: the DC bus is too high, usually because the motor is sending energy back.
  • Overcurrent: the output current is too high, so look at the motor, the cable or the load.

When does the drive trip?

VFD faults by moment: accelerating, steady speed and slowing down

The moment of the fault is your best clue. Check the drive’s fault history, which often records the speed, current and DC bus voltage at the time.

  • While accelerating: overcurrent is most likely.
  • At steady speed: overcurrent from a jam or a short circuit, or undervoltage from supply dips.
  • While slowing down: overvoltage is most likely.

Overcurrent (OC)

The drive measured more output current than it can safely deliver.

1. Acceleration time too short or load too heavy

A fast ramp asks the motor for a lot of torque and current. A heavy load, or a load that is stuck when starting, adds to this.
Fix: Increase the acceleration time and check that the load can move freely. Don’t just raise the current limit.

2. A mechanical jam or stalled motor

A jammed conveyor, a seized bearing or a blocked gearbox makes the current rise quickly, even at steady speed.
Fix: With the power locked out, turn the shaft by hand and look for mechanical resistance (see our guide on motors that won’t start).

3. A short circuit or ground fault in the motor or cable

Damaged cable insulation, water in the motor terminal box or a failed winding can cause a sudden, large current.
Fix: With the drive disconnected and locked out, test the insulation of the cable and the motor with a megohmmeter, and check the terminals.

4. Wrong settings or a drive that is too small

Incorrect motor data (current, voltage, frequency), too much torque boost or a drive that is undersized for the motor can cause overcurrent.
Fix: Compare the drive parameters with the motor nameplate, and check the drive’s rating against the motor and the load.

Overvoltage (OV)

The DC bus voltage rose above the drive’s limit.

5. Deceleration time too short

When a drive slows a heavy, spinning load quickly, the motor acts like a generator and pushes energy back into the DC bus.
Fix: Increase the deceleration time, or enable the drive’s overvoltage control function if it has one.

6. A load that drives the motor, with no braking resistor

Loads that keep pushing (going downhill, fans, flywheels) send energy back even at steady speed.
Fix: Fit a braking resistor, or use a drive that can return the energy to the supply. If one is already fitted, check the resistor, its wiring and its protection.

7. High supply voltage

A supply that is too high, or voltage spikes from other equipment, can push the DC bus over its limit.
Fix: A qualified person measures the supply voltage on all three phases, and checks for spikes and the settings of the supply transformer.

Undervoltage (UV)

The DC bus voltage fell below the drive’s limit.

8. Supply dips, phase loss or a weak supply

Short voltage dips, a missing phase, a blown input fuse or a large load starting on the same supply can drop the DC bus.
Fix: Check the supply voltage on all three phases (qualified person), the input fuses, the breaker and the connections. Some drives can ride through short dips if the function is enabled.

9. Loose connections or a failing drive

A loose input terminal, a faulty input contactor or a charging circuit problem can cause random undervoltage. In older drives, worn DC bus capacitors can also be the cause.
Fix: Check and retighten the input connections with the power locked out. If everything is correct and the fault remains, call the manufacturer or a drive specialist.

Step-by-step troubleshooting

Seven-step checklist for troubleshooting a VFD fault
  1. Read and write down the fault code, and check the fault history.
  2. Lock out the power and wait for the DC bus to discharge.
  3. Match the fault to the moment it trips: accelerating, steady speed or slowing down.
  4. For undervoltage or overvoltage, check the supply on all three phases, the fuses and the connections (qualified person).
  5. For overcurrent, check the motor and cable with an insulation test.
  6. Check the load and the ramp times, and the braking resistor if there is one.
  7. Review the motor data and limits in the parameters, then reset the drive once.

Mistakes to avoid

  • Raising the current limit to stop the trips. You hide the problem and can damage the motor or the drive.
  • Resetting again and again. Each restart on a real fault can stress the drive. Find the cause first.
  • Bypassing or removing the braking resistor because it is hot. It is doing its job.
  • Opening the drive too soon. Wait for the DC bus to discharge.

Quick reference

Fault When it usually appears First checks
Overcurrent (OC) While accelerating Ramp time, load, motor data
Overcurrent (OC) At steady speed Jam, motor and cable insulation
Overvoltage (OV) While slowing down Decel time, braking resistor, supply
Undervoltage (UV) Any time, often at random Supply, fuses, connections

When to call a specialist?

If the drive shows internal faults, if the same fault returns after you fixed the obvious causes, or if you aren’t sure how to work safely, stop and call a qualified technician or the manufacturer. A drive repair is cheaper than a second failure.

Which VFD brand do you work with, and which fault do you see most often? Share it in the comments below.


Print this checklist and keep it in your toolbox or your panel.

Download the free checklist (PDF)

Tuesday, October 20, 2026

Motor Running Hot: 8 Causes and a Troubleshooting Checklist

 

Motor running hot: 8 causes and a troubleshooting checklist

A motor that runs hot is not always a faulty motor. It is often the first sign of a problem somewhere else: too much load, poor cooling, a bad supply or a failing bearing. Left alone, the heat slowly destroys the winding insulation, and the motor fails long before it should. This guide explains how hot is too hot, the eight most common causes, and a checklist to find the real one.

Safety first: Don’t touch a motor that may be hot. Use an infrared thermometer. Lock out the power before opening terminal boxes, covers or fan guards. Current and voltage measurements on live equipment must only be done by a qualified person, following local rules.

How hot is too hot?



Maximum winding temperature for insulation classes B, F and H


Motors normally run warm. What matters is the temperature of the winding compared with the limit of its insulation class, which is written on the nameplate. Class B is rated for 130 °C, Class F for 155 °C and Class H for 180 °C (typical values at 40 °C ambient). These numbers apply to the winding inside, not to the outside housing, which reads cooler.

A useful rule of thumb: running about 10 °C above the insulation limit can roughly halve its life. So a motor that is “only a bit too hot” for a long time is still being damaged.

If you can’t comfortably keep your hand on the housing, that is a sign to measure, not to guess. Compare the reading with the nameplate and the manufacturer’s data.


Why motors overheat?

Heat generated and heat removed in a motor: why temperature rises

A motor’s temperature rises when it generates more heat than it can get rid of. Heat comes from the current in the windings, from magnetic losses and from friction. Cooling comes from the fan, the air around the motor and clean surfaces. Overheating means one side of that balance has gone wrong.

8 common causes

1. Overload or heavy duty

The motor draws more current than its nameplate value because the load is too high, or because it starts too often. Each start draws several times the normal current and heats the windings.
Fix: A qualified person measures the current on each phase and compares it with the nameplate. Reduce the load, or check the duty and the number of starts per hour.

2. Poor cooling

A blocked fan cover, a clogged cooling fin, a broken fan or a motor mounted in a hot, closed space can’t get rid of its heat.
Fix: With the power locked out, clean the fins and the air inlet, check the fan, and make sure there is free space around the motor. Check the ambient temperature too.

3. Voltage too low or too high

Low voltage makes the motor draw extra current to deliver the same power. Voltage that is too high increases magnetic losses.
Fix: A qualified person measures the voltage at the motor terminals while it runs and compares it with the nameplate. Fix the supply or the cable size.

4. Voltage imbalance or phase loss

When the three phases are not equal, the current imbalance can be many times greater than the voltage imbalance, and one winding overheats. A missing phase is the worst case.
Fix: Measure all three phases at the motor terminals (see our guide on motors that won’t start). Look for loose connections, worn contacts and unequal loads on the supply.

5. Worn or poorly lubricated bearings

Friction from a worn bearing, too little grease or too much grease creates heat, often concentrated at the end brackets, with noise or vibration.
Fix: Listen for noise, check the temperature at each end, and follow the manufacturer’s lubrication instructions. Replace worn bearings.

6. Misalignment or wrong belt tension

A misaligned coupling or a belt that is too tight puts extra load on the shaft and the bearings.
Fix: With the power locked out, check the alignment and belt tension against the machine’s instructions.

7. Running on a drive at low speed

On a motor driven by a variable frequency drive (VFD), a shaft-mounted fan moves less air at low speed, so cooling drops. The drive’s output can also add extra heating.
Fix: Check the speed range and the load at low speed. Use a motor made for drive use or add a separate cooling fan if the motor runs slowly for long periods.

8. Winding or insulation damage

Shorted turns, damaged insulation, moisture or contamination cause local overheating and higher current.
Fix: With the motor disconnected and locked out, measure the winding resistance and the insulation resistance with a megohmmeter, and compare them with the manufacturer’s values.

Step-by-step troubleshooting


Seven-step checklist for troubleshooting a motor that runs hot

  1. Measure the housing temperature with an infrared thermometer, not your hand.
  2. Compare the current on each phase with the nameplate (qualified person).
  3. Check the supply voltage and the balance between the phases (qualified person).
  4. With the power locked out, check the fan, the cover, the fins and the surroundings.
  5. Check the bearings and the alignment.
  6. If a drive is used, check the speed range and the cooling at low speed.
  7. Test the windings and the insulation with the motor disconnected.

Mistakes to avoid

  • Raising the overload relay setting to stop it from tripping. The motor will overheat instead of stopping.
  • Ignoring a motor that is only “a bit warm”. Long-term heat damages insulation silently.
  • Over-greasing the bearings. Too much grease creates heat, just like too little.

Quick reference

What you notice Likely cause
Current above nameplate value Overload, low voltage, mechanical problem
Hot motor, normal current Poor cooling, high ambient, slow-speed running
One end bracket hotter, noise Worn bearing, lubrication or alignment
Unequal currents between phases Voltage imbalance, loose connection, winding fault
Burnt smell, low insulation resistance Damaged winding or insulation

When to call a specialist

If the insulation test fails, the motor smells burnt, or you can’t find the cause, stop and call a qualified electrician or a motor repair shop. A rewind or a new motor costs far less than a breakdown in the middle of production.

Have you found a surprising reason why a motor was overheating? Share it in the comments below.


Print this checklist and keep it in your toolbox or your panel.

Download the free checklist (PDF)