Circuit Breaker Keeps Tripping: 8 Causes in an Industrial Panel

Circuit breaker keeps tripping: 8 causes in an industrial panel

A circuit breaker that keeps tripping is doing its job: it opens when something is wrong. Resetting it again and again, or fitting a bigger one, hides the problem and can lead to damaged equipment or a fire. This guide explains how to read the trip, the eight most common causes in an industrial panel, and a step-by-step way to find the real one.

Safety first: A short circuit can cause an arc flash when you re-energize, and a breaker that has cleared a large fault may be damaged. Lock out the power, verify it is dead, and follow your company’s procedures and protective equipment rules. Measurements and thermal checks on live panels must only be done by a qualified person.

Reading the breaker handle

Breaker handle in the ON, tripped and OFF positions
A breaker handle has three positions. ON means closed, OFF means open by hand, and a tripped breaker usually rests in a middle position between the two. To reset a tripped breaker, move the handle fully to OFF first, then to ON. Reset it once, and only after you have checked for an obvious cause. If it trips again immediately, leave it off and investigate.

Which kind of trip is it?

Thermal, magnetic and earth leakage trips compared: how they trip, what they mean and what to check


Most breakers combine different protections, and how the breaker tripped is your best clue:

  • Thermal (overload): it trips after some time, often minutes after a load starts, and the breaker may feel warm. The current was above the rating for too long.
  • Magnetic (short circuit): it trips instantly, often with a loud bang. There was a very high fault current between conductors.
  • Earth leakage (ground fault): it trips instantly or at random, often in damp conditions. Current is leaking to earth.

8 common causes

1. Overload

The circuit carries more current than the breaker rating for too long, for example a motor with a mechanical problem, or loads added to an existing circuit.
Fix: A qualified person measures the load current on each phase and compares it with the breaker rating. Find out why it is high (see our guide on motors running hot, and the one on voltage imbalance).

2. Short circuit

Damaged cable insulation, a failed component, metal debris or a loose strand of wire can create a direct short between conductors. The breaker trips instantly.
Fix: With the power locked out, inspect the circuit and test the insulation resistance between phases and to earth. Don’t reset until you find the cause, and check the breaker for damage afterward.

3. Ground fault or earth leakage

Moisture in a motor terminal box, damaged cable insulation or a failing winding lets current flow to earth. Drives and their filters also create small leakage currents, which can trip an earth leakage device that is not suited for them.
Fix: Test the insulation to earth with a megohmmeter. Check for water and damage. If a drive is involved, ask the manufacturer which type of earth leakage protection is suitable.

4. Starting current and the wrong trip curve

Motors and transformers draw a large inrush current at start. A breaker with a fast curve may trip each time, even if the circuit is healthy.
Fix: Check that the breaker type and curve suit the load. For motors, a motor protection breaker is often the right device. Follow the design or the manufacturer’s data.

5. Loose connections and overheating

A loose lug or busbar connection creates resistance and heat. The breaker heats up from the connection and trips at a lower current than its rating.
Fix: With the power locked out, retighten connections as specified and look for discoloration. A thermal camera, used by a qualified person on the live panel, helps to find hot spots.

6. High temperature or crowded breakers

Thermal breakers are sensitive to the temperature around them. In a hot, closed enclosure, or when many breakers are mounted side by side, they can trip below their rated current.
Fix: Check the enclosure temperature and ventilation. Check the manufacturer’s derating data for grouped breakers.

7. Wrong or changed settings

On breakers with adjustable trip units, someone may have changed the current or time settings, or the settings may not match the load after a change to the plant.
Fix: Compare the settings with the design values. Don’t raise them to stop the tripping without an engineering check.

8. A worn or damaged breaker

Breakers wear out. After a large fault, or after years of use, a breaker can trip below its rating or fail to hold.
Fix: If everything downstream checks out and the breaker still trips, test or replace it. Use a breaker of the same type and rating.

Step-by-step troubleshooting

Seven-step checklist for troubleshooting a circuit breaker that keeps tripping

  1. Note how the breaker tripped: handle position, trip flag and the time after starting.
  2. Lock out the power and look for heat marks, a burnt smell and damaged cables.
  3. Check the breaker rating, curve and settings against the load.
  4. Test the insulation downstream, phase to phase and phase to earth.
  5. Check terminals and temperature (qualified person).
  6. Measure the load current and compare it with the rating (qualified person).
  7. Reset once, then reconnect the loads one at a time and test.

Mistakes to avoid

  • Resetting again and again. Each reset onto a fault is a risk.
  • Fitting a bigger breaker. The cable and the equipment are then no longer protected.
  • Raising the trip settings without an engineering check.
  • Ignoring a warm breaker. Heat means a problem somewhere in the connection.
  • Bypassing the breaker in any way.

Quick reference

What you notice Likely cause
Trips after minutes under load, breaker warm Overload, heat, loose terminal
Trips instantly when closed Short circuit or ground fault
Trips when a motor starts Inrush current, wrong curve or setting
Trips at random, often in damp conditions Earth leakage, moisture, drive filters
Trips below its rating and runs hot Loose connection, high ambient, worn breaker

When to call a specialist?

If the breaker trips immediately after a reset, if you smell burning or see damage, or if you can’t find the cause, stop and call a qualified electrician. A fuse that keeps blowing follows similar logic, so see our guide on fuses that keep blowing.

Which kind of trip have you seen most often in your plant? Share it in the comments below.